Call 800-593-4042My account
Product specifications

APC AP7801B power distribution unit (PDU) 8 AC outlet(s) 1U Black

Review the specifications, then ask our team for current pricing and availability.

Metered, 1U, 20A, 120V, 50/60 Hz, 8x NEMA 5-20R, NEMA L5-20P, 444 x 102 x 44 mm, 1730 g

Part AP7801B · UPC 731304331469

Catalog availability is a file snapshot. Call to confirm stock and pricing before ordering.

Add to cart Continue browsing

About this product

Availability

Alarm Thresholds

Define alarm thresholds in order to avoid overloaded circuits. Network and visual alarms inform the user of possible problems. (Note: Only available on units with the current monitoring capabilities. Please see SKU specifications for availability)

Local Current Monitoring Display

The aggregate current draw per rack PDU is displayed on the unit via a digital display. The local digital display helps installers avoid overloaded circuits by providing a visible warning when the current draw is close to the maximum amperage draw of the strip. (Available on designated SKUs only)

Integrates with StruxureWare Data Center Expert

An IT-ready, scalable access monitoring system that collects, organizes, and distributes critical alerts, surveillance video and key information, providing a unified view of complex physical infrastructure environments from anywhere on the network

Load indicator LED

Indicates overload and warning conditions based on the user-defined alarm thresholds. Alerts users of potential overloaded circuits.

Flash Upgradeable

Quickly and easily upgrade firmware via network download for future product enhancements. Eliminates the need to replace products already installed in the field when new features are released. (Note: Networked units only)

Remote Management Capabilities

Full-featured network management interfaces that provide standards-based management via Web, SNMP, and Telnet. Allows users to access, configure, and manage units from remote locations to save valuable time. Associated with this feature is the ability to quickly and easily upgrade the firmware via network download to installed units for future product enhancements.

Agility

Rack-Mountable

Includes horizontal, vertical, and toolless-mount varieties. Puts power where it is needed most - in the racks near the equipment.

Single input power source

Supply power from one branch whip to multiple pieces of equipment, conveniently powering rack-mount equipment. Saves time and money during installation by using one branch whip and standard connections.

Wide range of input and output connections

Product family includes a variety of input and output connections to distribute 120V, 208V, or 230V power to multiple outlets. Having a variety of inputs and outputs allow users to adapt to varying power requirements. APC offers units that bring up to 14.4kW using a single branch whip.

Marketing Features

Load indicator LED

Indicates overload and warning conditions based on the user-defined alarm thresholds. Alerts users of potential overloaded circuits.

Local Current Monitoring Display

The aggregate current draw per power distribution unit is displayed on the unit via a digital display. The local digital display helps installers avoid overloaded circuits by providing a visible warning when the current draw is close to the maximum amperage draw of the strip.

Local and web-based monitoring

Status available to customers both in the data center and remotely

Wide range of input and output connections

Product family includes a variety of input and output connections to distribute 120V, 208V, or 230V power to multiple outlets. Having a variety of inputs and outputs allow users to adapt to varying power requirements. APC offers units that bring up to 14.4kW using a single branch whip.

Alarm Thresholds

Define alarm thresholds in order to avoid overloaded circuits. Network and visual alarms inform the user of possible problems.

Manufacturer warranty information

2 years repair or replace

Design

PDU types
Metered
Rack capacity
1U
Product colour
Black

Ports & interfaces

AC outlets quantity
8 AC outlet(s)
AC outlet types
NEMA L5-20R
Input connection type
NEMA L5-20P

Features

LED indicators
Yes
Cable length
3.66 m

Management features

Monitoring
Current

Power

Nominal input voltage
100-120 V
AC input frequency
50 - 60 Hz
Maximum current
20 A
Nominal output voltage
120 V
Load capacity
1920 VA
Maximum input current per phase
20 A
Maximum total current draw per phase
16 A

Certificates

Compliance certificates
RoHS
Certification
cUL, CSA, FCC 15 A, ICES-003, UL 60950, UL

Operational conditions

Operating temperature (T-T)
-5 - 45 °C
Storage temperature (T-T)
-25 - 65 °C
Operating relative humidity (H-H)
5 - 95%
Storage relative humidity (H-H)
5 - 95%
Operating altitude
0 - 3000 m
Non-operating altitude
0 - 15000 m

Weight & dimensions

Width
444 mm
Depth
102 mm
Height
44 mm
Weight
1.73 kg

Packaging data

Package weight
2.91 kg
Package width
470 mm
Package depth
337 mm
Package height
64 mm

Specifications and images: Database Right data-sheet 2026 Icecat. All rights reserved. Supplied as is, without warranty. Specs Icecat · Open Content License

Development preview

Review your request.

No message has been sent. This draft stays on this device.